2 channels 16-bit analog input (current 0~20mA/4~20mA; voltage 0~5V/0~10V), PID function 2 channels PT100 temperature signal input, temperature precision0.01℃, PID function 2 channels 10-bit voltage output DC-DC power insulation, enhanced noise immunity ability. Each channel has one group of PID parameters, PID function. FROM and TO instruction for reading and writing the data General specifications: Item | Analog input (AD) | Temperature input(PT) | Voltage output (DA) | Analog input | Current | 0~20mA, 4~20mA | PT100 | - | Voltage | 0~5V, 0~10V | Temperature range | - | -100~327℃ | - | Safety range of max input | DC0~40mA | - | - | Analog output range | - | - | Voltage | 0~10V, 0~5V | Current | 0~20mA, 4~20mA | Digital input range | - | - | 10-bit binary (0~1023) | Digital output range | 16-bit binary (0~65535) | -10000~32767 | - | Resolution | 1/65535 (16Bit) | 0.01℃ | 1/1023(10Bit) | PID output | 0~K4095 | - | Integrated precision | 0.8% | ±0.01℃ | 0.8% | Transformation speed | 20ms/1 channel | 3ms/1 channel | Power for analog | DC24V±10%,100mA | Mounting method | Fixed with M3 strews or directly installed in DIN46277(35mm width) guide rail | |